8.3.3.5
Combustion Dynamics Monitoring (CDM)
Inputs 1-8 support CDM sensors to collect wideband dynamic pressure. Inputs 1-3 also collect dynamic pressure magnitude
relative to a specified frequency in RPM. Combustion Dynamics applications rely on the higher bandwidth and enhanced
algorithms which are only implemented in the YVIBS1B.
Attention
CDM Sensors are only supported on the YVIBS1B.
CDM Input Processing
GAPn_VIBn – Sensor biasing voltage in Volts.
Gap values are filtered through a 2-pole, low-pass filter with a fixed cutoff frequency of 8 Hz. The output of the gap filter is
passed through a rolling average filter prior to scaling. For CDM sensors, the gap value is not scaled, and it will remain in
Volts. This value can be used to monitor sensor health.
Gap
Filter
Mvg
Avg
Filter
V
GAP
V
FILT
GAPn_VIBn
V
PROX
VIBn – Wideband Dynamic Pressure (pk-pk or RMS) in engineering units (EU).
Wideband dynamic pressure information is passed through 1-pole, high-pass filter with a fixed cutoff frequency of .1Hz. This
removes static pressure prior to wideband filtering. This data is passed through the wideband filter, which can be configured
as a low-pass, high-pass, or band-pass filter. The high-pass and low-pass filters can be configured for 2, 4, 6, 8, or 10 pole
Butterworth filters with a user-defined cutoff (-3dB) point.
Depending on the value of the VIB_CalcSel for each input, the filtered data will be used to provide pk-pk dynamic pressure
within the scan period, or RMS dynamic pressure within the scan period.
For pk-pk dynamic pressure calculations, the wideband filter output is sent through a variable length pk-pk detection function.
The length of the pk-pk detection is determined by the CDM_Scan_Period value in configuration.
The output of the pk-pk detection function (VPK-pk) is passed through an adjustable 1-pole, low-pass filter prior to scaling.
VPK-pk is converted from Volts to EU.
Note
A lower latency pk-pk detection function can be enabled by changing the
OperatingMode
parameter to Enhanced.
This function will update every frame, instead of every scan period.
For RMS dynamic pressure calculations, the wideband filter output is captured into a variable length buffer. The length of the
RMS calculation is determined by the CDM_Scan_Period value in configuration.
The data in the buffer is used to compute an RMS voltage (VRMS) over that capture length, which is passed through an
adjustable 1-pole, low-pass filter prior to scaling (this filter cannot be disabled). VRMS is converted from Volts to EU.
Note
Sensors monitoring dynamic pressure typically measure RMS. Peak calculations can be used instead for legacy
applications.
Note
RMS calculations are not available with YVIB systems.
YVIB Vibration Monitor Modules
GEH-6855_Vol_II System Guide 257
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...