Point Unhealthy Troubleshooting (continued)
Digital Input
Internal Wetted Input exceeded range of
operation
Check field wiring. Measure incoming mA signal and verify that it is 10
mA.
Digital Input
External Wetted Input exceeded range of
operation
Check field wiring. Measure voltage across digital inputs terminal points
and verify it is between -1 V and 21 V.
Digital Input
NAMUR input exceeded range of operation
Check field wiring. Verify mA signal through field device does not exceed
9 mA. Replace the field device.
Digital Input
Digital Input mode configured as wrong type
Verify field wiring and field device matches the configured Input Mode
found in the ToolboxST application.
Digital Input
Open circuit detected on digital input signal
Check the wiring between the terminal board and the device. Verify that
the recommended line monitoring resistors are being used.
Digital Input
Short detected on digital input signal
Check the wiring between the terminal board and the device. Verify that
the recommended line monitoring resistors are being used.
Pulse
Accumulator
Pulse input voltage exceeds the limits of the
YUAA hardware
Check field wiring. Measure incoming signal and verify that it is within -11
V and 21 V. Replace the field device.
96
Description
Invalid calibration settings
Possible Cause
•
Calibration file not detected
•
Calibration file corrupted
•
Calibration constants invalid
•
Hardware Failure
Solution
Replace the I/O pack.
97-98
Description
Cold Junction temp [ ] exceeds range limit ([ ])
Possible Cause
Cold junction input to the analog-to-digital converter exceeded the limits of the converter. If a cold
junctions fails, the
CJ_Backup
value is used.
Solution
•
Check the mounting of the I/O pack on the terminal board.
•
Replace the terminal board.
•
Replace the I/O pack.
218
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...