Attention
This mode of input uses low currents due to the load resistance. If the user’s contact
cannot support under 1 mA of current flow, use the YDIA/STCI combination with 2.5
or 10 mA current flow.
This mode of input cannot support a field supply higher than 30 V. If 48 V or 125 V
operation is desired, use the appropriate YDIA/STCI combination supporting that
supply level.
7.10.3
Internal Wetted Contact Inputs
The switch is connected between PWR_RET and IO+, where the channel’s DAC output is passed via the external switch
circuit to IO+ into the burden resistor. There are two types of external switch circuits supported as follows:
•
Simple switch only
•
Line monitoring (open/short detection) with the switch having two resistors in parallel and series
For the simple switch, the channel DAC is set for the contact current to flow from PWR_RET through the switch to IO+ into
the 250 ohm burden resistor to ground. The decision on switch state is based on current above or below 50% the set value as
measured on the burden resistor.
For line monitoring with detection of an open connection compared to an open switch, the DAC is set in voltage output mode
by firmware. The user adds two resistors to limit the current in normal operation with both set at the same value based on the
choice of desired current through the contact.
Internal Wetted Simple Contact
Internal Wetted Contact with Line Monitoring (Open/Short) Wire Detection
The variations on internal fed switches have the following contact voltages and currents.
Line Monitoring
Disabled
Enabled
Contact current
10 mA
10 mA
Set by channel DAC in current output mode
Set by resistors, DAC is set to 5V
Resistor values (equal, 1% tolerance)
None
240 ohm ¼ watt
I/O+ for contact closed
2.5V
2.55
Open Contact voltage
Up to 24V
1.64
I/O+ for contact open
0
1.71
Threshold volts at IO+ for open loop
None
0.86
Threshold volts at IO+ for contact decision
1.25
2.13
Threshold volts at IO+ for short
None
3.78
198
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...