GE Power Management
LPS-O Line Protection System
8-
19
8 LOCAL USER INTERFACE
8.2 INFORMATION
8
The detailed status information is presented starting from the third line. The user may use the arrow keys to
scroll through the information. Each time the arrow key is pressed, a full screen of detailed status information is
displayed. Status information is presented in the following order: critical failure information, non-critical failure
information and miscellaneous status information.
8.2.3 REQUEST FAULT INFORMATION
This category is used to display fault information.
When this category is selected, a summary of the fault information for the stored faults is displayed to facilitate
the user choose a fault for viewing more information about it. An example is shown below:
where: XXX: Fault type
YYY: Trip type
MM/DD HH:MM: Date and time of occurrence
The number in the top right-hand corner indicates the selected fault. When the category is entered, the number
is #1 and the cursor is on the first fault. The arrow keys may be used to scroll through the list of accumulated
faults. The number on the top line will change to match the currently selected fault. The user can also enter the
fault number to view. If the number is valid when the user presses [ENT] key, the cursor will be placed on the
selected fault description. An error message is displayed if the user enters an invalid number.
The user has to press [ENT] key to view all the fault information. An example is shown below:
Explanation of the information displayed for each fault is given below:
Time: HH:MM:SS.XXX (XXX = msec) – time of fault occurrence
Date: MM/DD/YY – date of fault occurrence
Fault Type: XXX – see the list below
Trip Type: YYY – see the list below
Distance: zzz.z MI/KM – distance to fault occurrence
Relay Op Time: xxxxxx – relay operating time in msec.
Brkr Op Time: xxxxxx – breaker opening time in msec.
Fault Types:
AB
(phases A-B)
BC
(phases B-C)
CA
(phases C-A)
3PH
(3-phase)
SELECT FAULT #1
XXX YYY MM/DD HH:MM
XXX YYY MM/DD HH:MM
XXX YYY MM/DD HH:MM
FAULT #1
Time: HH:MM:SS.XXX
Date: MM/DD/YY
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...