LPS-O Line Protection System
GE Power Management
5.1 MEASURING UNIT TESTS
5 FUNCTIONAL TESTS (FACTORY SETTINGS)
5
5.1.2 T1 – FAULT DETECTOR TEST
The Fault Detector responds to sudden changes in current levels. Slow changes are not picked up.
1.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–16.
2.
Set the relay into test mode 22 (the fault detector). The LUI displays
FAULT DETECTOR ON
3.
Protection Settings:
Z1DISTANCE
(101)
Z1PHASE = NO
Z2DISTANCE
(201)
Z2PHASE = NO
Z3DISTANCE
(301)
Z3PHASE = NO
Z4DISTANCE
(401)
Z4PHASE = NO
OVERCURRENT
(601)
50 = NO
(605)
50G = NO
(610)
51G = NO
4.
Set the voltages to zero.
5.
Slowly increase
I
op
to 1.2 (0.24) A rms, at approximately 0.1 (0.02) A per second. Slowly decrease the cur-
rent to 0 A. The A1 contact should not close.
6.
Immediately increase
I
op
to 1.5 (0.3) A rms. The A1 contact should close momentarily.
7.
Immediately increase
I
op
to 2.5 (0.5) A rms. The A1 contact should close until current is removed.
8.
Reduce
I
op
to 0.
5.1.3 T2 – IT TRIP SUPERVISION TEST
1.
Protection Setting:
CURSUPVISN
(501)
IT_PICKUP = 0.25 (0.05) Amps
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–16.
3.
Set the relay into test mode 18 (IT Detector). The LUI displays:
IT DETECTOR ON
4.
Set the voltages to zero.
5.
Set
I
op
to 0.35 (0.07) A rms and apply to the relay. The A1 contact should close. Lower
I
op
to 0.15 (0.03) A
rms, at which point the A1 contact should open.
6.
Reduce
I
op
to 0.
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...