4 ACCEPTANCE/PERIODIC TESTS
4.2 GENERAL RELAY TESTS
4
4.2 GENERAL RELAY TESTS
4.2.1 T1 – RELAY STATUS AND DISPLAY TESTING
The LPS-O Status is reported through the Keypad/Display Interface, the noncritical alarm contact, and the crit-
ical alarm contact. If a system error causes relaying functions to cease, the status LED turns red and the criti-
cal alarm contact closes. A failure that does not interrupt relaying is indicated by closing the noncritical alarm
contact and displaying a WARN message and green status LED.
a) STATUS CHECK
This test demonstrates the use of the Keypad/Display Interface to check relay status. See Chapter 11: LPSO-
LINK USER GUIDE or Chapter 12: ASCII COMMUNICATIONS for further details.
1.
Only the DC power supply voltage is required for this test. Apply the rated DC power and wait for initializa-
tion to complete (if this has not been done already), as indicated by the green LED.
2.
Press the [INF] key, then use the arrow keys to scroll until the cursor in on
1. LPS STATUS
3.
Press the [ENT] key. The display should contain the message
STATUS: OK
indicating that the relay is operational and there are no errors.
4.
Verify the setting of the trip circuit monitor (General Setting 107: NUM_MON) is:
NUM_MON = 0011
Be sure to press the [END] and [ENT] keys after the setting is changed. When this is done, the relay
expects wetting voltage across the trip contacts T1 and T2.
5.
Press the [INF] key and scroll with arrow keys until the display contains the message:
1. LPS STATUS
6.
Press the [ENT] key. The display should contain the message
STATUS: FAIL
FAIL: TRIP CKT #1 CONTINUITY
ERROR
This verifies that the relay detected the absence of wetting voltage across the trip contact.
7.
Change the setting of the trip circuit monitor to
NUM_MON = 0000
to re-check the status. The display should read
STATUS: OK
8.
Change the setting of the trip circuit monitor back to NUM_MON = 0011 before starting the next test.
b) DISPLAY AND KEYPAD TESTS
The Keypad/Display Interface (LUI) Test is built into the software and allows testing the keypad and the display.
1.
Apply rated DC power and wait for initialization to complete, as indicated by the green LED, if necessary.
2.
Press the [ACT] key, then scroll with the arrow keys until the display contains the heading
7. LUI TEST
3.
Press the [ENT] key. The display should contain three choices to test the display, LEDs and keypad.
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...