Table 2–9: PROTECTION SETTINGS DATA SHEET (Sheet 1 of 7)
No.
M nem onic
Description
Range (5A)
Range (1A)
User
Setting
Z1DISTANCE
101
Z1PHASE
Z1 Phase Distance
NO, YES
NO, YES
102
Z1PHREACH
Z1 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
104
Z1P_TIME
Z1 Phase Timer
0.00 to 10. sec.
step 0.01
0.00 to 10. sec.
step 0.01
Z2 DISTANCE
201
Z2PHASE
Z2 Phase Distance
NO, YES
NO, YES
202
Z2PHREACH
Z2 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
203
Z2PCHARANG
Z2 Phase Characteristic
Angle
90 to 120 deg.
step 5
90 to 120 deg
step 5
204
Z2TIMER
Z2 Timer
NO, YES
NO, YES
205
Z2P _TIM E
Z2 Phase Timer
0.00 to 10.0 sec.
step 0.01
0.00 to 10.0 sec.
step 0.01
Z3DISTANCE
301
Z3PHASE
Z3 Phase Distance
NO, YES
NO, YES
302
Z3PHREACH
Z3 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
303
Z3PCHARANG
Z3 Phase Characteristic
Angle
90 to 120 deg.
step 5
90 to 120 deg
step 5
304
Z3P_TIME
Z3 Phase Timer
0.00 to 10.0 sec.
step 0.01
0.00 to 10.0 sec.
step 0.01
Z4DISTANCE
401
Z4PHASE
Z4 Phase Distance
NO, YES
NO, YES
402
Z4PHREACH
Z4 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
403
Z4PCHARANG
Z4 Phase Characteristic
Angle
80 to 120 deg.
step 5
80 to 120 deg
step 5
404
Not Used
405
Z4_TIMERS
Z4 Timers
NO, YES
NO, YES
406
Z4 P _T IM E
Z4 Phase Timer
0.00 to 10.0 sec.
step 0.01
0.00 to 10.0 sec.
step 0.01
see TABLE NOTES on page 2–53 for footnote explanations
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...