2 CALCULATION OF SETTINGS
2.3 PROTECTION SETTINGS
2
801: LINEPICKUP - Select Line Pickup
Set LINEPICKUP = YES if the line pickup logic is to be used, otherwise set LINEPICKUP = NO.
802: BYPASSTL3 - Bypass Line Pickup Time Delay
If simultaneous reclosing is used and if I1PICKUP (Protection Setting 803) must be set below full load, then set
BYPASSTL3 = NO, otherwise set BYPASSTL3 = YES.
803: I1PICKUP - I1 Pickup Setting
I1 is the overcurrent trip unit used in the Line Pickup function, and it operates on the magnitude of the posi-
tive-sequence current.
I1PICKUP should be set no greater than two-thirds of the minimum fault current for an internal three-phase
fault at the relay location. If the minimum fault current is greater than the maximum load current on the pro-
tected line, then the I1 setting can be reduced to provide greater coverage of the line. For this case, a setting of
110% of the maximum load current is proposed.
2.3.10 REMOTEOPEN
The Remote-Open Detector (ROD) function issues a trip signal when the remote breaker opens during an
unbalanced internal fault. This function detects that the remote breaker has opened by recognizing charging
current on one or more phases following opening of the remote breaker. The Remote-Open Detector will not
operate for a balanced three phase fault.
ROD logic can speed up tripping at the end of the line that otherwise would be the slowest to respond in a
sequential-tripping condition. In a Step Distance scheme, ROD tripping is beneficial for any unbalanced inter-
nal fault not detected by Zone 1. Figure 2–9: ROD LOGIC DIAGRAM is a functional logic diagram of the ROD
function. The sequence of events that results in an ROD output is as follows:
Figure 2–9: ROD LOGIC DIAGRAM
1.
No charging current is detected prior to the fault – logic 0 output from AND2.
2.
A fault is detected – logic 1 output from OR3.
3.
The remote breaker opens and charging current is detected – logic 1 output from AND3.
4.
The fault is still present, so the two inputs to AND4 persist and a trip output will be produced following the
time-delay setting of timer TL20.
A
0
I A L E A D S
V A B Y 9 0 °
I B L E A D S
V B B Y 9 0 °
I C L E A D S
V C B Y 9 0 °
F A U L T
D E T E C T O R
A N Y Z O N E 2
P H A S E - D I S T A N C E
F U N C T I O N
1
1
2
2
4
3
A = 10 to 100
T L 2 0
T R I P
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...