2-
44
LPS-O Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
2.5.3 GENERAL SETTINGS GUIDE
Table 2–8: GENERAL SETTINGS GUIDE (Sheet 1 of 3)
No.
M nem onic
Description
Range
(5A & 1A)
Step
Default
CONFIGURE
101
U N ITID
Unit ID
0000 to 9999
1
0000
102
SYSFREQ
System Frequency
50 Hz, 60 Hz
none
60Hz
103
PHASROTATE
Phase Rotation
ABC, ACB
none
ABC
104
TIMESYNCH
Time Synch Source
INTERNAL, IRIG-B
none
INTERNAL
105
NUM_BKR
Number of Breakers
1, 2
none
1
106
NUM_TC
Number of Trip Circuits
1, 2
none
1
107
NUM_MON
Number of Trip Circuit
Monitors
(T4
→
T1)
format = abcd
a-d = 0 (on) or
1(off)
0000 (0)
T1 to T4 off
108
DISPLAYVAL
Value Display Mode
PRI, SEC
none
SEC
109
LANGUAGE
Language Option
ENGLISH, SPANISH
none
ENGLISH
COMMPORTS
201
C O M P O R T 1
Communications Port #1
Settings
Baud Rate (xx),
Parity (y), Stop Bits
(z)
format = xxyz
xx = 03, 12, 24, 48,
96, 19;
y = 0 (none), 1
(odd), 2 (even);
z = 1, 2
9601
202
COMPORT2
Communications Port #2
Settings
Interface (i), Baud
Rate (xx), Parity (y),
Stop Bits (z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03,
12, 24, 48, 96, 19;
y = 0 (none), 1
(odd), 2 (even);
z = 1, 2
09601
203
COMPORT3
Communications Port #3
Settings
Interface (i), Baud
Rate (xx), Parity (y),
Stop bits (z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03,
12, 24, 48, 96, 19;
y = 0 (none), 1
(odd), 2 (even);
z = 1, 2
09601
204
PROTOCOL1
Communications Port #1
Protocol
GE-MODEM, ASCII
none
GE-MODEM
205
PROTOCOL2
Communications Port #2
Protocol
GE-MODEM, ASCII
none
GE-MODEM
206
PROTOCOL3
Communications Port #3
Protocol
GE-MODEM, ASCII
none
GE-MODEM
‡
Contact Converter output normally appears as a Logic 1 with normally open contact connected; to invert
output to Logic 0, add 1000 to the number
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...