GE Power Management
LPS-O Line Protection System
6-
15
6 FUNCTIONAL TESTS (USER SETTINGS)
6.4 BACKUP PROTECTION TESTS
6
6.4.2 T15 – 3 PHASE FAULT WITH TRANSFORMER COMPENSATION
1.
Protection Settings:
Z1DISTANCE
(101)
Z1PHASE= YES
(102)
Z1PREACH = [________]
Ω
(104)
Z1P_TIME = 0.0 sec.
Z2DISTANCE
(201)
Z2PHASE = NO
Z3DISTANCE
(301)
Z3PHASE = NO
Z4DISTANCE
(401)
Z4PHASE = NO
LINEINFO
(1204) TRSFMRTYPE = YD1
2.
Connect the relay as shown in Figure 5–2: THREE PHASE TEST CONNECTIONS. Set the relay to test
mode 14 (Any Zone 1 Phase). The LUI displays:
ANY Z1 PHASE ON
3.
Set the voltage inputs to the following values:
VA: 67 volts rms
∠
0°,
VB: 67 volts rms
∠
–120°,
VC: 67 volts rms
∠
+120°.
4.
Select a value for
V
NOM
between 30 and 50 V rms:
V
NOM
= [________] V rms
5.
For a three phase fault, we have the following equation:
(eq. 6–8)
6.
Set the current inputs to the following values:
IA:
IB:
IC:
7.
Reduce the voltage of all three phases simultaneously to
V
NOM
V rms and check that the A1 contact
closes.
8.
If desired, repeat the test for Zone 2, 3, or 4 by setting the specific zone reach and disabling the zone ele-
ments not being tested.
I
V
Z
----
V
NOM
Z
R
---------------
=
=
V
NOM
Z
R
---------------
[________] Amps rms
79.6
°
–
∠
=
V
NOM
Z
R
---------------
[________] Amps rms 160.4
°
∠
=
V
NOM
Z
R
---------------
[________] Amps rms 40.4
°
∠
=
Содержание LPS-O
Страница 2: ......
Страница 4: ......
Страница 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Страница 40: ...1 26 LPS O Line Protection System GE Power Management 1 10 ELEMENTARY DIAGRAM 1 PRODUCT DESCRIPTION 1 ...
Страница 112: ...3 16 LPS O Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 166: ...6 16 LPS O Line Protection System GE Power Management 6 4 BACKUP PROTECTION TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 200: ...8 32 LPS O Line Protection System GE Power Management 8 4 REMOTE COMMUNICATION INTERFACE 8 LOCAL USER INTERFACE 8 ...
Страница 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Страница 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 280: ...13 18 LPS O Line Protection System GE Power Management 13 4 CREATING XPRESSION BUILDER LOGIC 13 XPRESSION BUILDER 13 ...
Страница 284: ...A 4 LPS O Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Страница 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Страница 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Страница 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Страница 307: ...GE Power Management LPS O Line Protection System NOTES ...