Main and Extended Menus
Part 17997
Rev. 6, March 2011
4-25
Table 4-7 - Electrical Current Generated by the Analog Output for Each Operation Mode
4.5.7.5
TDM Out
•
TDM State
: Displays the state of the Hydran 201T
i
’s TDM signal, in percentage.
– Used with the H201C
i
-1 Controllers only, the TDM signal is integrated to the
supervisory link and is used to transmit the state of the H201T
i
’s alarm relays and
analog output. Only one pair of wires is necessary to transmit this information. For
details on the supervisory link, see Section 9.1 on page 9-1.
– The TDM signal relates to the gas level being measured. The displayed percentage is
thus directly proportional to the gas level (% output = ppm/20; 2,000 ppm = 100 %).
•
TDM
Mode
: Is used to set the operation mode of the TDM signal. The three
Force x %
modes are used only to test the operation of the Hydran 201
i
System.
4.5.8
NewSensor Submenu (Extended Menu Only)
The
NewSensor
submenu is used to:
• Set the Hydran 201 sensor parameters.
• Install a new H201 sensor.
This submenu is very similar to the
Service;SensorCal Data
submenu (see Section 4.5.4.1
on page 4-18), except that in the latter submenu the parameter values cannot be changed.
The
NewSensor
command requires password No. 2. The H201 sensor is then immediately
tested and the result (
Good
or else) is displayed after three seconds. For details, see
Operation Mode
Analog 4–20 mA Output
Hydran 201C
i
-1 Display
Force 0 %
4.00 ± 0.10 mA
0 ± 2 ppm
Force 50 %
12.00 ± 0.20 mA
1000 ± 5 ppm
Force 100 %
20.00 ± 0.40 mA
1999 ppm
a
a.
The maximum value of the Hydran 201Ci-1’s display scale is 1999 ppm. If the signal is over
scale, the display indicates 1... when the operation mode is set to Force 100 %.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......