Chapter 2 • Hydran 201T
i
Intelligent Transmitter
2-14
Rev. 6, March 2011
Part 17997
The sensor signal is in microvolts (µV). It is first divided in two scales; then, these two
signals go through the analog/digital converter and finally the two digital values are read
by the microprocessor. The two scales are:
• Low scale, which ranges from 0 to 4,000 µV.
• High scale, which ranges from 0 to 40,000 µV.
The thermistor signals are in ohms (
; 3,000
at 25 °C). These two signals also go
through the analog/digital converter and are then read by the microprocessor.
2.5.2
Analog Output
The isolated (up to 2,000 V RMS) analog 4–20 mA current output can supply a load
ranging from 0 to 500
(10 V maximum). It is used with a SCADA system.
For details on how to use the analog output, see Appendix G; for wiring details, see
Table D-6 on page D-3.
2.6
HEATING SYSTEM
The recommended operating temperature range of the Hydran 201 sensor is 15 to 65 °C (59
to 149 °F). The sensor temperature is a function of:
• The ambient air temperature surrounding the Hydran 201T
i
.
• The oil temperature behind the valve on which the H201T
i
is mounted.
Note: This temperature is always lower than the oil temperature at the top of the
transformer tank.
• The thermal regulation of the H201T
i
’s temperature.
Regardless of the oil or ambient temperature, the H201T
i
is designed (heating and passive
cooling) to maintain the sensor temperature between 25 and 45 °C (77 and 113 °F), if the
set-point (
Temp SetPoint
parameter in the
Temperature;DynOil Sampl
submenu; see
Section 4.5.3 on page 4-17) is set to the recommended temperature of 35 °C (95 °F).
The H201T
i
’s microprocessor measures the temperature and controls the heating power. A
fail alarm is triggered (if on; see the
FaultTrig.
parameters in Section 4.5.7.3 on page 4-24)
when the sensor temperature is outside the operating limits.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......