Chapter 8 • Hydran 201C
i
-1 Installation
8-14
Rev. 6, March 2011
Part 17997
8.3.7
Installing the ac Power Supply Cable
1.
Run the three-wire ac power supply cable through a conduit up to the
Hydran 201C
i
-1.
2.
Connect the cable to terminals 1 and 2 of the main terminal block, and connect the
E/G
wire to the enclosure chassis. For wiring details, see Table D-11 on page D-8.
3.
Connect the other end of the cable to the power source.
4.
If desired, connect the H201T
i
’s ac power supply cable to terminals 4 to 6 of the main
terminal block.
8.3.8
Verifying the Operation
Proceed as described in Section 8.2.1 on page 8-3 and Section 8.2.2 on page 8-3.
8.3.9
Verifying the Analog Outputs
Perform this procedure only if the Hydran 201C
i
-1’s analog outputs are used (connected to
a SCADA system).
Proceed as described in Section 8.2.3 on page 8-4.
CAUTION
WARNING
ELECTRICAL SHOCK HAZARD. Turn off the electric power at the
fuse box or service panel before making any electrical connections,
and ensure a proper ground connection is made before connecting
line voltage. Failure to do so can result in property damage, personal
injury and/or death.
CAUTION
WARNING
The earth/ground terminal (terminal 3) must be connected. Never
perform high-voltage tests (mega-ohm measurements using a
Megger* instrument) on cables connected to a Hydran 201Ti or a
Hydran 201Ci Controller. Never apply high voltages to the
components of a Hydran 201R Model i, as they are equipped with
surge protection devices that could be damaged by Megger* tests.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......