Verification of Operation Prior to Installation
Part 17997
Rev. 6, March 2011
8-3
8.2.1
Preparation
To verify its operation, the Hydran 201C
i
-1 must first be connected to a functional
Hydran 201T
i
via a supervisory link cable. One end of this cable is already connected to
the H201T
i
. For details on commissioning the H201T
i
, see Chapter 6. Proceed as follows:
1.
Connect a three-wire power cord to the ac Power 3-Terminal Block on the H201T
i
(item 8 in Figure 2-4 on page 2-8): The live side to
L1/L
, the other side to
L2/N
, and
the ground to
E/G
. For additional wiring details, see Table D-1 on page D-1.
2.
Connect the second end of the three-pair supervisory link cable coming out of the
H201T
i
to the main terminal block on the H201C
i
-1 (item 6 in Figure 3-6 on
3.
Power On the H201T
i
.
4.
Ensure the H201T
i
is operating normally and no gas or fail alarms are present, by
looking at the small LED indicators on the right side of the I/O module (refer to
Section 2.4.6.3 on page 2-11).
5.
Connect a power cord to the terminals 1 and 2 on the main terminal block of the
H201C
i
-1 (item 6 in Figure 3-6 on page 3-11), and connect the
E/G
wire to the
enclosure chassis.
6.
Power On the H201C
i
-1.
8.2.2
Initial Observations
1.
Verify the Hydran 201C
i
-1’s display is not blank. If it remains blank, the possible
causes are as follows:
• If the fail alarm is triggered, read the alarm message on the Hydran 201T
i
’s display to
identify the cause of the alarm. Then see Chapter 12.
• Verify the connections at both ends of the supervisory link cable.
• Verify the fuse(s) and the ac power supply of the H201C
i
-1 and H201T
i
.
• Verify the operation of the H201C
i
-1’s display.
2.
Verify the H201C
i
-1’s display shows the same ppm value as the H201T
i
’s scrolling
gas level display. A discrepancy of ± 2 ppm is acceptable.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......