Chapter 6 • Hydran 201T
i
Installation
6-26
Rev. 6, March 2011
Part 17997
• Conduits, or cable armors, should be made of steel to shield against magnetic fields.
• Nonconducting conduit fittings (made of plastic, for example) can be used on the
connection box if ground loops through the conduits may cause problems (for example,
if the transformer tank is grounded at a single point and monitored continuously for tank-
to-ground currents).
The procedure is as follows:
1.
Remove the cover from the connection box located under the brass adaptor.
2.
As required, install one or two watertight conduit fittings (not supplied) onto the
connection box.
• One conduit is used to run the supervisory link cable (which connects the H201T
i
to the
Hydran 201C
i
Controller) and, if used, the cable of the H201T
i
’s analog output.
• One conduit is used to run the power supply cable and, if used, the cable of the H201T
i
’s
alarm contacts.
3.
Mount a conduit to each fitting.
Note: The ac power to the H201Ti can be supplied from the H201Ci-1 Controller (via
terminals 4 to 6 of the main terminal block) or from a different source. The H201Ci-C does
not have terminals used to supply power to the H201Ti.
4.
Ground the conduits and/or cable shields at some point. Follow the company
regulations meticulously.
6.3.9
Installing the Supervisory Link and Analog Output Cable
Note the following considerations prior to installing:
• The supervisory link cable is supplied only when the Hydran 201T
i
is part of a
Hydran 201R Model
i
or is ordered with a Hydran 201C
i
-C Controller.
• A supervisory link cable connected to a H201C
i
-1 requires three twisted pairs and an
overall shield.
CAUTION
WARNING
The H201Ti must always be grounded, even if the transformer tank
is grounded at a single point and monitored for tank-to-ground
currents.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......