Installation Overview
Part 17997
Rev. 6, March 2011
5-13
5.2.4
Cabling and Network Configuration
Several Hydran 201C
i
Controllers installed in a station can be linked together using an
RS-485 link to form a local network. A local network of Hydran 201
i
Systems can include
up to 32 H201C
i
Controllers and 128 Hydran 201T
i
’s. The H201C
i
Controllers
(Hydran 201C
i
-C’s and/or Hydran 201C
i
-1’s) can all be connected together. The network
configuration is explained in Chapter 9.
Any H201C
i
Controller in a local network can be connected to a host computer (running
the General Electric Canada’s Hydran Host software) through an RS-232 or USB link to
monitor all the H201T
i
’s in the network. The host computer and the network can also
communicate through a modem, thus allowing remote monitoring.
To maximize the benefits of a network, simple guidelines should be followed. Use the
following rules to install and implement a network of Hydran 201
i
Systems.
5.2.4.1
Parameter Settings
1.
The parameters of each H201T
i
(identification number, power station identification
number, communication speed, alarm set points, operation mode of relays, etc.) must
be selected before field installation.
2.
Each H201T
i
of a local network must be set to an individual and exclusive identifi-
cation number (parameter
H201Ti ID
in the
Communication
submenu) selected
between 1 and 254. The numbers can be assigned sequentially or using any other
method preferred by the user.
If two H201Ti’s share the same number in a local
network, they are not able to communicate properly with the host computer.
It can be
useful to assign numbers that correspond to the identification numbers of the trans-
formers being monitored; for an example, see Table 5-1 on page 5-14.
3.
All H201T
i
’s belonging to a local network must share a common power station
identification number (parameter
PowerStat. ID
in the
Communication
submenu).
This number is used when accessing a station remotely, or when analyzing and
displaying historic data in the Hydran Host software.
4.
All H201T
i
’s in a local network must be set to the same data communication speed
(parameter
BaudRate
in the
Communication
submenu; 1,200, 2,400, 4,800 or
9,600 bps). The recommended speed is 9,600 bps.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......