Chapter 4 • Hydran 201T
i
’s Displays and Menus
4-16
Rev. 6, March 2011
Part 17997
4.5.2
Gas Submenu
The
Gas
submenu allows the user to set the parameters of the conditions that trigger:
• The gas alarm: A High or High-High alarm is triggered if an alarm condition (
GasLevel
,
HourlyTrend
or
DailyTrend
)
exceeds
the corresponding High or High-High alarm set
point for a period of time greater than the delay.
• The fail alarm: It is triggered if an alarm condition (
GasLevel
,
HourlyTrend
or
DailyTrend
)
is below
the corresponding Low or Low-Low alarm set point for a period
of time greater than the delay.
The operation of the alarms is explained in detail in Chapter 10.
4.5.2.1
Gas Level
This function gives access to the gas level High and High-High alarm parameters:
•
GasLevel
: Current reading of gas level, in ppm. Same value as the one shown in the
Main Display mode.
•
GasAlr H
: Set point of gas level High alarm.
•
GasAlr HH
: Set point of gas level High-High alarm.
•
GasAlr Delay
: Alarm delay for all gas level alarms’ set points.
•
GasAlr L
(Extended Menu only): Set point of gas level Low alarm.
•
GasAlr LL
(Extended Menu only): Set point of gas level Low-Low alarm.
4.5.2.2
Hourly Trend
This function gives access to the hourly trend High and High-High alarm parameters:
•
HourlyTrend
: Current reading of hourly trend, in ppm/x hours. Same value as the one
shown in the Main Display mode.
•
HourTrAlr H
: Set point of hourly trend High alarm.
•
HourTrAlr HH
: Set point of hourly trend High-High alarm.
•
HourTrAlr Delay
: Alarm delay for all hourly trend alarms’ set points, in % of the
period.
•
HourlyTr Period
(Extended Menu only): Period of the hourly trend (number of hours
used to calculate the gas level variation).
•
HourTrAlr L
(Extended Menu only): Set point of hourly trend Low alarm.
•
HourTrAlr LL
(Extended Menu only): Set point of hourly trend Low-Low alarm.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......