Chapter 6 • Hydran 201T
i
Installation
6-14
Rev. 6, March 2011
Part 17997
11.
Modify the
Temp Setpoint
by pushing
CHANGE
.
12.
When asked to enter the password #1 (
1253
), use the
UP
and
ENTER
keys.
13.
Decrease the
Temp Setpoint
to 30 °C (86 °F) using the
UP
and
ENTER
keys.
14.
Return to a previous level of the menu by pushing
ESC
.
15.
Re-enter the menu using the
DOWN
or
UP
key.
16.
Check the
Temp Setpoint
has changed to 30 °C (86 °F).
17.
When all is done, push
END
.
Note: Reset the Temp Setpoint to 35 °C (95 °F), the default value.
6.2.8
Verifying the Analog Output (Facultative)
Table 4-7 on page 4-25 lists the values of the electrical current that should be generated for
each operation mode.
1.
Connect a suitable dc digital ammeter with a 1 % accuracy and a 0.01 mA resolution
to the terminal screws 7 (
+
) and 8 (
-
) of the Supervisory Link and Analog Output
Termination Board (see item 9 in Figure 2-4 on page 2-8). Refer to Table D-6 on
page D-3 for connection details.
2.
Access the top of the extended menu by pushing
ENTER
twice (
History
appears).
Note: Once accessed, the extended menu times out after 30 minutes of keypad inactivity.
3.
Push
DOWN
six times until
Relays/Analog
appears.
4.
Access this menu by pushing
ENTER
.
5.
Push
DOWN
three times until
Analog out
appears.
6.
Read the analog output state by pushing
ENTER
. The value should be close to 0 %.
7.
Push
DOWN
to access
Analog Out Mode
. The value should be
Normal
.
Содержание Hydran 201i
Страница 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Страница 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 72: ...Chapter 3 Hydran 201Ci Controllers 3 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Страница 176: ...Chapter 8 Hydran 201Ci 1 Installation 8 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 190: ...Chapter 9 Communications and Networking 9 14 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 216: ...Chapter 11 Operating the Hydran 201i System 11 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Страница 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Страница 262: ...Appendix C Functional Block Diagrams C 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 282: ...Appendix F Default Values of the Parameters F 4 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Страница 299: ......