CHAPTER 2: INSTALL ATION/CONFIGURATION
2.42
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
If the “soft stop time activated” parameter is set, the by-pass relay 43 will open immediately after the OFF
command is received, and after the soft stop timer expires, output relay 41 opens, K1 opens, and removes
power to the soft starter and motor.
The soft stop timer is set on WinESG parameterization/timer panel and/or Modbus holding register 37
NOTE:
Ensure soft starter is located before contactor.
If the default configuration and the soft starter typical are selected in the WinESG
parameterization/information shown in the illustration below or by setting Modbus function code 6 register 62
bit0 to 1 and bits 8,9,10 and 11 to 0x4,the inputs and outputs are mapped as below:
For EntelliPro ES5 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to main circuit feedback
- active low
Input 97 is mapped to by-pass contactor feedback
- active high
Input 96 is mapped to up-to-speed feedback
- active high
Input 95 is mapped to emergency circuit
- active low
Input 94 is mapped to external supervision
- active high
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to contactor 1
Output 43 is mapped by-pass contactor
Output 45 is mapped to reset alarm
For EntelliPro ES5 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to by-pass contactor feedback
- active high
Input 97 is mapped to reset alarm
- active high
Input 96 is mapped to up-to-speed feedback
- active high
Input 95 is mapped to starter fault feedback
- active low
Input 94 is mapped to main circuit feedback
- active low
Input 93 is mapped to control circuit feedback
- active low
Input 11 is mapped to command OFF
- active low
Input 12 is mapped to command ON1
- active high
Input 13 is mapped to drawer position test
- active high
Input 14 is mapped to external fault 1
- active high
Input 15 is mapped to drawer position operation
- active high
Input 16 is mapped to emergency stop
- active low