CHAPTER 2: INSTALL ATION/CONFIGURATION
2.12
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
Register
Description
Bit Definition
115
Bit0 thru Bit2 defines the Remote source
Bit0 – Bit 2
Bit4 thru Bit6 defines the source that controls the local/
remote/ off switch
Bit 0- bit 2
0 - None
1 - Profibus Class 1
2- Modbus
3-Hardwire
0- None
1- Profibus Class 1
2-Modbus
3-Hardwaire
4-Fixed Local
5-Fixed Remote
Table 2-5 Remote source and switch control selection via Modbus
To start contactor1, Modbus command function code 5 register 11 set to ON selects the remote source
(Modbus), as a means to control the start/stop/reset operations. This command may be issued only once
upon power up.
Once the remote selection is made, a start command can be issued using Modbus function code 5 register
1.
To start contactor2, Modbus command function code 5 register 11 set to ON selects the remote source
(Modbus), as a means to control the start/stop/reset operations.. Once the remote selection is made a start
command can be issued using Modbus function code 5 register 2.
To start the contactors, Modbus command function code 5 register 10 set to ON selects the local sources
(hardwire, Modbus RTU and WinESG), as a means to control the start/stop/reset operations. This command
may be issued only once upon power up.
Once the local selection is made, a start command can be issued from any local sources.