CHAPTER 2: INSTALL ATION/CONFIGURATION
2.20
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
2.3 Motor Starter Configuration
There are eleven pre-programmed starter types (typicals), which can be selected via Modbus RTU or Profibus
communication..
The following are the starter types:
Full-voltage non-reversing
Full-voltage reversing
Star-delta open transition
Star-delta reverse open transition
Soft starter
Reverse soft starter
Breaker Control
(see note below)
Dahlander
Pole changer
Solenoid valve
Actuator with limit or torque switch
In additional customers can order customized motor starter arrangement by providing GE with desired logic control for
inputs, outputs and timers.
NO
TE:
NOTE
:
Customer can change pre-defined configurations of any motor starter if the default configuration is
not
to simulate the application.
Breaker Control selection is NOT available on EntelliPro ES Revision 1.002. Custom logic can be created to
selected.
To select the motor starter type via Modbus, holding register 62 bit 8 to 11 should be used. Refer to Chapter 4 for
additional Modbus information. WinESG
parameterization/information panel shown in the illustration below can be
used to configured the motor starter type.
WARNING:
If
“allow
direction
switchover”
is
enabled,
make
sure
the
“motor
ON
direction
switchover
time”
timer
exceeds
the
contactor
or
breaker
clearing
time
to
avoid
short
circuit.