CHAPTER 4: COMMUNICATION
4.40
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
Size
Telegram Name
Description
Default
Bytes
Unit
Scale
2
BIT0 - Safety circuitStatus
BIT1 - EntelliPro Local Mode Status
BIT2- EntelliPro Remote Mode Status
BIT3 - Drawer Operation Mode Status
BIT4- Drawer Test Mode Status
BIT5 - Limit Switch1 Status
BIT6 - Limit Switch2 Status
BIT7- General Device Error Status
1 indicates that safety circuit input is set. Input must be mapped.
1 indicates that switch position is set to local. If hardwire is
contrlling the switch then digital input must be mapped.
1 indicates that Switch position is set to remote. Input must be
mapped.
1 indicates that drawer is in operation mode. Input must be
mapped.
Also configurion telegram B40001 43 bit 3 -
ActivateDrawerPositionSupervision must be set.
1 indicates that drawer is in test mode. Input must be mapped
ActivateDrawerPositionSupervision must be set.
1 indicates that limit switch 1 is set.
1Indicates that limit switch2 is set.
1 indicates there is a general device error.
3
BIT0 - Feedback_IdentificationStatus
BIT1 - Class1Failure
BIT2 - ModbusFailure
BIT3 - ByPassSwitchedON
BIT4 - Switching1Progress
BIT5 - Switching2Progress
BIT6 - Breaker Tripped 2
BIT7 -Status Charged
1 indicates the feedback from identification command - output
must be mapped optional as soon as the ID command is issued
this bit is set.
1 indicates Profibus Class1 failure
1 indicates Modbus failure
1 indicates by-pass switch on. Input must be mapped.
1 indicates switching is progress. Input must be mapped as well as
the corresponding output.
1 indicates switching is progress. Input must be mapped as well as
the corresponding output.
1 indicates Breaker tripped. Input must be mapped.
1 indicates status charge. Input must be mapped.
4
BIT0 - TorqueSwitching1Progress
BIT1 - TorqueSwitching2Progress
BIT2 -Start Phase
BIT3 -RunPhase
BIT4 - ThermistorLineBroken
BIT5-ThermistorLineShorted
BIT6 - Free
BIT7 - Free
1 indicates torque switching is in progress. Input must be mapped
as well as the corresponding output.
1 indicates torque switching is in progress. Input must be mapped
as well as the corresponding output.
1 indicates the motor is in the start phase.
1 indicates that the morot is in the run phase.
1 indicates thermistor line open.
1 indicates thermistor line shorted.
Содержание EntelliPro ES Series
Страница 2: ...This page was intentionally left blank ...
Страница 8: ...This page was intentionally left blank ...
Страница 182: ...CHAPTER 4 COMMUNICATION EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 4 45 This page was intentionally left blank ...
Страница 255: ...EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 6 20 CHAPTER 6 ENTELLIPRO CP3 and CP5 APPLICATION ...