CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.41
If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to
mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor
(ON/OFF). If input mode switch remote is active, the mechanism defined as remote can control the motor (ON/OFF).
If Fixed local is selected as a controlling device, any source assigned as local can control the motor (ON/OFF).
If Fixed remote is selected as a controlling device, only the remote source can control the motor (ON/OFF).
NOTE:
only one control (local or remote) can be enabled at a time. If both (local and remote) are active the “drawer
ready switch” will be OFF and the motor cannot start.
NOTE:
to make any changes on the configuration, “parameter allowed” must be enabled in WinESG
parameterization/function panel or Modbus function code 6 register 62.
Refer to section 2.2.1 for the motor control detailed configuration.
Soft starter operation:
when an ON1 command is received, contactor K1, controlled by EntelliPro output relay 41, will
close. This provides power for the soft starter to start and power to drive the motor. When the soft starter signals up-
to-speed by closing relay UTS, the starter generates the soft starter bypass signal and the EntelliPro ES relay 43 is
then closed.
If bypass the control is activated in WinESG parameterization/timer panel or Modbus function code 6 register 111
bit6, an alarm will be generated when the “soft starter timer” set on WinESG parameterization/timer panel or
Modbus function code 6 register 36 expires prior to the bypass input signal.
NOTE:
an input must be mapped to by-pass feedback.
When an OFF command is received and the soft stop is activated in WinESG parameterization/timer panel or Modbus
function code 6 register 111 bit5, contactor relay output 43 opens, signaling the soft starter to ramp down.
The opening time of contactor K1, controlled by EntelliPro ES output relay 41, is dependent on the configuration of
“soft stop time activated” parameter set in WinESG parameterization/timer panel or Modbus function code 6 register
111 bit5,
Содержание EntelliPro ES Series
Страница 2: ...This page was intentionally left blank ...
Страница 8: ...This page was intentionally left blank ...
Страница 182: ...CHAPTER 4 COMMUNICATION EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 4 45 This page was intentionally left blank ...
Страница 255: ...EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 6 20 CHAPTER 6 ENTELLIPRO CP3 and CP5 APPLICATION ...