CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.43
Input 17 is mapped to safety circuit
- active low
Input 18 is mapped to mode switch local
- active high
Input 19 is mapped to mode switch remote
- active high
Output 41 is mapped to contactor 1
Output 43 is mapped to by-pass contactor
Output 45 is mapped to ATEX redundancy contactor
Output 22 is mapped to local control
Output 23 is mapped to On1 command (start)
Output 24 is mapped to reset
Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)
Output 26 is mapped to failure
NOTE:
If default configuration box is left un-checked, the user will have the ability to change the mapping and other
parameters.
NOTE
: Ensure soft starter is located before contactor.
Refer to Tables 2-6 and 2-7 for the complete input , output , timer and control configurations of the Soft starter.
Figures 2-18 and 2-19 show typical softstarter diagrams for EntelliPro ES3 and EntelliPro ES5.
Figure 2-18 EntelliPro ES3 Softstarter starter wiring diagram