CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.85
Motor Starter Standard Configuration
EntelliPro ES5
Full-voltage
non-
reversing
Full-voltage
reversing
Star-delta
non-
reversing
Star-delta
reversing
Softstarter
Softstarter
reversing
Breaker
Dahlander
Polechanger
Actuator
Solenoid
Valve
Feedback via contact
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Feedback via current
N/A
Activated
Activated
Activated
Activated
Activated
N/A
Activated
Activated
Activated
N/A
Direct Switch over without OFF
command
N/A
Deactivated
N/A
Deactivated
N/A
Deactivated
N/A
Activated
Activated
Deactivated
N/A
Current depending YD Switch Over
N/A
N/A
Activated
Activated
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Soft Stop Timer
N/A
N/A
N/A
N/A
Deactivated
Deactivated
N/A
N/A
N/A
N/A
N/A
Bypass Control
N/A
N/A
N/A
N/A
Activated
Activated
N/A
N/A
N/A
N/A
N/A
External Soft Starter Fault
N/A
N/A
N/A
N/A
Activated
Activated
N/A
N/A
N/A
N/A
N/A
MCCB Tripped 2 Configuration (Alarm
or No-Alarm)
N/A
N/A
N/A
N/A
N/A
N/A
No alarm
N/A
N/A
N/A
N/A
Breaker Trip Reset from EntelliPro ES
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
N/A
N/A
N/A
MCCB Feedback
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
N/A
N/A
N/A
Torque Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Enable
N/A
Switch OFF at Limit Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
Switch OFF at Current Threshold
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Deactivated
N/A
Switch OFF at Torque Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Deactivated
N/A
Enable Modbus RTU Control
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable Profibus DP Class 2 Control
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable Hardwired Control
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
bit 1 - Class1 n bit 0r (n+1) bit
n bit
n bit
n bit
n bit
n bit
n bit
n bit
n bit
n bit
n bit
n bit
bit 2 - Level/Edge
Level
Level
Level
Level
Level
Level
Level
Level
Level
Level
Level
bit 3 - Inverted OFF / Non-Inverted
OFF
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
bit 1 - Hardwire n bit 0r (n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
bit 2 - Hardwire Level/Edge
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Thermistor Line Broken/Shorted
Supervision.
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Drawer Position Supervision
Activated
Activated
Activated
Deactivated
Activated
Deactivated
Deactivated
Activated
Activated
Deactivated
Activated
Drawer Position 1 bit Modus / 2 bit
Modbus
2 bit
2 bit
2 bit
N/A
2 bit
N/A
N/A
2 bit
2 bit
N/A
2 bit
Modbus Failure Detection
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
ATEX Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Activated
bit 5 - Remote OFF always valid
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
bit 6 - Block Local Switch ON
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Alarm Setting
Overload
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
Enable
Enable
Phase Loss
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Ground Fault
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Unbalance Load
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Thermsitor
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Emergency Stop
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Limit Switch
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Enable
Enable
Safety Circuit
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Main Circuit
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Control Circuit
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Switch Position
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Underload Current
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Overload Current
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
External Supervisory
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Long Start Time
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Input Mapping
Input 99 Mapping
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
MCCB ON
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Input 99 High/low Activation
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Input 98 Mapping
not used
Y Contactor
Feedback
Contactor 2
Feedback
Contactor 2
Feedback
Bypass
Feedback
Contactor 2
Feedback
Breaker
Ready to
Switch ON
Contactor 2
Feedback
Contactor 2
Feedback
Contactor 2
Feedback
Drawer
position Test
Input 98 High/Low activation
N/A
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Содержание EntelliPro ES Series
Страница 2: ...This page was intentionally left blank ...
Страница 8: ...This page was intentionally left blank ...
Страница 182: ...CHAPTER 4 COMMUNICATION EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 4 45 This page was intentionally left blank ...
Страница 255: ...EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 6 20 CHAPTER 6 ENTELLIPRO CP3 and CP5 APPLICATION ...