CHAPTER 5: WinESG
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
5.2
2
Figure 5-13-: WinESG parameterization control panel
Control configuration in illustration A enables and disables the source, defines the sources as local or remote, and defines
the mode of operation of the source (1-bit or 2-bit). Only one source can be set as a remote. The rest, if enabled, will be
automatically set as local.
Profibus DP (PB DP C1):
Profibus class 1 cyclic communication such as PLC, can be set as
1-
Bit (level) or 2-Bit (edge), Inverted OFF or Non-Inverted OFF.
1 – Bit:
ON-bit (telegram B10008 bit0 or bit1) will turn the motor ON and OFF.
2-Bit:
ON-bit (telegram B10008 bit0 or bit1) will turn the motor ON and OFF-bit
(telegram B10008 bit0 or bit14) will turn motor off.
Inverted OFF:
active low signal (0) is valid OFF command.
Non-Inverted OFF:
active high signal (1) is valid OFF command.
Remote selection:
selects the remote source – Profibus class 1, Modbus or hardwire
NOTE:
if Profibus Class 1 is enabled it is assigned as a remote.
NOTE:
When changing from 1-bit to 2-bit it is recommended that the power be re-cycled.
NOTE:
If hardwire is set to 1-bit and remote source is hardware it is not recommend to keep remote Off valid,
since it is an invalid combination.
Remote OFF in Local control: valid - Remote source can stop a motor
invalid - Remote source cannot stop a motor