CHAPTER 1: INTR ODUCTION
1.14
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
1.2.7 Testing and certification
Test Reference Standard Test Level
Dielectric voltage withstands ...................................
..
.....1.5kV
Impulse voltage withstand ..............................................EN60255-5
Electrostatic discharge.......................................................EN61000-4-2/IEC60255-22-2 Level 4
RF immunity ............................................................................EN61000-4-3/IEC60255-22-3 Level 3
Fast transient disturbance ...............................................EN61000-4-4/IEC60255-22-4 Class A
Surge immunity ................. ..................................................EN61000-4-5/IEC60255-22-5 Level 3
Conducted RF immunity ....................................................EN61000-4-6/IEC60255-22-6 Level 3
Radiated and conducted emissions.............................CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal vibration ...........................................................IEC60255-21-1 Class 1
Voltage dip and interruption ..........................................IEC61000-4-11 0, 40, 70% dips, 250/300 cycle interrupts
Harmonics ..................................................................
.
...........IEC61000-4-13
Voltage ripple ........................................................................IEC61000-4-17 15% ripple
Environmental (cold)................................................. .........IEC60068-2-1 -25° C,
9
6 hrs
Environmental (dry heat) .................................................IEC60068- 2-2 70° C,
9
6 hrs
Relative humidity cyclic ...................................................IEC60068- 2-30 6-day variant 2
Short-circuit current*.........................................................IEC60947-5-1
ATEX certificati
o
Rated impulse withstand voltage ............................4kV
(
when EntelliPro ES is
not
directly connected to the main voltage)
(when
EntelliPro ES is
directly connected to the main voltage)
Over
vol
tage category
II according to IEC 60947-1 7.2.3.1 item 2) b)
Pollution degree...................................................................
I
Overvoltage category III according to IEC 60947-1 7.2.3.1 item 2) b)
SIL1
Profibus certification
*CAUTION:
A maximum A7DQS or gl 10A fuse is required on motor relays.