CHAPTER 2: INSTALL ATION/CONFIGURATION
2.68
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
When limit switch 2 is reached (input 96 on EntelliPro ES3 and input 19 on EntelliPro ES5) a “switch position” warning or
a fault will be generated.
CAUTION:
The phase system in WinESG parameterization\device settings panel shown in the illustration below or
Modbus function code 6 register 5 must be set to 1 phase if the system is a 1 phase system for proper overload
protection.
If the default configuration and the solenoid typical are selected in the WinESG parameterization/information panel
shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to
0x9,the inputs and outputs are mapped as below:
For EntelliPro ES3 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to main circuit
- active low
Input 97 is mapped to limit switch 1 reached
- active low
Input 96 is mapped to limit switch 2 reached
- active low
Input 95 is mapped to emergency stop
- active low
Input 94 is mapped to external supervision
- active high
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to contactor 1
Output 43 is mapped to command ON1 (start)
Output 45 is mapped to failure
Содержание EntelliPro ES Series
Страница 2: ...This page was intentionally left blank ...
Страница 8: ...This page was intentionally left blank ...
Страница 182: ...CHAPTER 4 COMMUNICATION EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 4 45 This page was intentionally left blank ...
Страница 255: ...EPOS MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL 6 20 CHAPTER 6 ENTELLIPRO CP3 and CP5 APPLICATION ...