GE Multilin
B30 Bus Differential System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
47EA
Breaker 1 Block Close
0 to 4294967295
---
1
F300
0
47EC
Breaker 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
47EE
Breaker 1 Phase B Opened
0 to 4294967295
---
1
F300
0
47F0
Breaker 1 Phase C Opened
0 to 4294967295
---
1
F300
0
47F2
Breaker 1 Operate Time
0 to 65.535
s
0.001
F001
70
47F3
Breaker 1 Events
0 to 1
---
1
F102
0 (Disabled)
47F4
Reserved
0 to 65535
s
1
F001
0
47F5
...Repeated for Breaker 2
481A
...Repeated for Breaker 3
483F
...Repeated for Breaker 4
4864
...Repeated for Breaker 5
4889
...Repeated for Breaker 6
FlexCurves A and B (Read/Write Settings)
4910
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
4988
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256
items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
“ “
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
Field Unit Raw Data Actuals (Read Only) (8 modules)
4E00
Raw Field Data AC1 Mag
0 to 0.001
A
0.001
F003
0
4E02
Raw Field Data AC1 Angle
0 to 0.1
degree
0.1
F002
0
4E03
Raw Field Data AC2 Mag
0 to 0.001
A
0.001
F003
0
4E05
Raw Field Data AC2 Angle
0 to 0.1
degree
0.1
F002
0
4E06
Raw Field Data AC3 Mag
0 to 0.001
A
0.001
F003
0
4E08
Raw Field Data AC3 Angle
0 to 0.01
degree
0.1
F002
0
4E09
Raw Field Data AC4 Mag
0 to 0.001
A
0.001
F003
0
4E0B
Raw Field Data AC4 Angle
0 to 0.01
degree
0.1
F002
0
4E0C
Raw Field Data AC5 Mag
0 to 0.001
A/V
0.001
F003
0
4E0E
Raw Field Data AC5 Angle
0 to 0.01
degree
0.1
F002
0
4E0F
Raw Field Data AC6 Mag
0 to 0.001
A/V
0.001
F003
0
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 60)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...