10-8
B30 Bus Differential System
GE Multilin
10.4 SLOPES AND HIGH SET THRESHOLD
10 APPLICATION OF SETTINGS
10
where
I
p
is the maximum CT primary fault current
The figure illustrates the K
s
CT saturation capability curve and K
S_LIM
limiting factor.
Figure 10–5: DETERMINING CT TIME-TO-SATURATE
CT time-to-saturate (t
SAT
) is determined as a projection of the intersection of the K
s
CT saturation capability curve and
K
S_LIM
CT limiting factor, as shown in the figure.
Practically, CT time-to-saturate can be obtained by either of the following methods:
•
Method 1 — Download the "CT Time-to-Saturate Estimator.xlsm" spreadsheet from the GE Multilin web site, located
under Support > Support Documents > B30 Bus Differential System. Enter the required system and CT parameters to
obtain the CT time-to-saturate.
•
Method 2
•Define several time instances t
1
, t
2
...t
n
•Use equation 10-5 to calculate the corresponding K
S1
, K
S2
…K
Sn
•Calculate K
S_LIM
using equation 10-7
•Compare each K
S
value with K
S_LIM
. If K
S
at the given time instance t
i
is less than K
S_LIM
, it means that true t
SAT
is
greater than t
i
, otherwise it is less than t
i
Columns 6 and 7 of the table below summarize the DC saturation threat for the fault on C-1. CT-4, CT-6, CT-7, and CT-8
may saturate due to the DC components and may generate spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 5.02 ms and will be detected by the Satura-
tion Detector.
The transient saturation of the CTs due to the DC component may be neglected when setting the slopes of the characteris-
tic as the saturation is detected and the relay uses the current directional principle. It must, however, be taken into account
when setting the high set (unbiased) differential element.
Table 10–4: EXTERNAL FAULT CALCULATIONS ON C-1
CT
I
FAULT
(KA)
I
FAULT
(A SEC)
T
DC
(MS)
AC
SATURATION
DC
SATURATION
T
SAT
(MS)
CT-1
14.0
116.67
40
Yes
Yes
5.02
CT-2
0
0.00
N/A
No
No
N/A
CT-3
6.0
25.00
5
No
No
N/A
CT-4
5.0
25.00
30
No
Yes
26.37
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...