GE Multilin
B30 Bus Differential System
9-9
9 THEORY OF OPERATION
9.5 SATURATION DETECTOR
9
Figure 9–8: SATURATION DETECTOR STATE MACHINE
NORMAL
SAT := 0
EXTERNAL
FAULT
SAT := 1
EXTERNAL
FAULT and CT
SATURATION
SAT := 1
The differential
characteristic
entered
The differential-
restraining trajectory
out of the differential
characteristic for a
certain period of time
saturation
condition
The differential
current below the
first slope for a
certain period of
time
836729A1.CDR