B-36
B30 Bus Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00
Ground Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5D01
Ground Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5D02
Ground Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5D03
Ground Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod
Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0
(Instantaneou
s)
5D07
Ground Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5D09
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5D0A
Ground Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5D0B
Reserved (6 items)
0 to 1
---
1
F001
0
5D11
...Repeated for Ground Time Overcurrent 2
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
5D44
...Repeated for Ground Time Overcurrent 5
5D55
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (6 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5DA1
Ground Instantaneous Overcurrent 1 Signal
Source
0 to 5
---
1
F167
0 (SRC 1)
5DA2
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5DA3
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5DA5
Ground Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5DA7
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
5DB1
...Repeated for Ground Instantaneous Overcurrent
2
5DC2
...Repeated for Ground Instantaneous Overcurrent
3
5DD3
...Repeated for Ground Instantaneous Overcurrent
4
5DE4
...Repeated for Ground Instantaneous Overcurrent
5
5DF5
...Repeated for Ground Instantaneous Overcurrent
6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group
1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through
6 (5 items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 60)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...