GE Multilin
B30 Bus Differential System
1-17
1 GETTING STARTED
1.4 UR HARDWARE
1
1.4UR HARDWARE
1.4.1 MOUNTING AND WIRING
See Chapter 3: Hardware for mounting and wiring instructions.
1.4.2 COMMUNICATIONS
The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether-
net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the computer COM2 port as described in
the
CPU communications ports
section of chapter 3.
Figure 1–7: RELAY COMMUNICATION OPTIONS
To communicate through the B30 rear RS485 port from a computer RS232 port, the GE Multilin RS232/RS485 converter
box is required. This device (catalog number F485) connects to the computer using a straight-through serial cable. A
shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the B30 rear communications port. The converter
terminals (+, –, GND) are connected to the B30 communication module (+, –, COM) terminals. See the
CPU communica-
tions ports
section in chapter 3 for details. The line is terminated with an R-C network (that is, 120
Ω
, 1 nF) as described in
the chapter 3.
1.4.3 FACEPLATE DISPLAY
All messages are displayed on a backlit liquid crystal display (LCD) to make them visible under poor lighting conditions.
While the keypad and display are not actively being used, the display defaults to user-defined messages. Any high-priority
event-driven message automatically overrides the default message and appears on the display.
EnerVista
Ethernet
10/100 Mbps
Regional
control
center
Modem
Remote
communications link
Local
control
Engineer
GE Multilin F485
communications converter
UR-series IED
Troubleshooting
Commissioning
Setting changes
Reports
RS485 115 kbps
RS232
EnerVista
EnerVista
842759A2.CDR
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...