GE Multilin
B30 Bus Differential System
B-73
APPENDIX B
B.4 MEMORY MAPPING
B
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F141
ENUMERATION: SELF TEST ERRORS
902
User-Programmable Pushbutton 3
903
User-Programmable Pushbutton 4
904
User-Programmable Pushbutton 5
905
User-Programmable Pushbutton 6
906
User-Programmable Pushbutton 7
907
User-Programmable Pushbutton 8
908
User-Programmable Pushbutton 9
909
User-Programmable Pushbutton 10
910
User-Programmable Pushbutton 11
911
User-Programmable Pushbutton 12
912
User-Programmable Pushbutton 13
913
User-Programmable Pushbutton 14
914
User-Programmable Pushbutton 15
915
User-Programmable Pushbutton 16
920
Disconnect switch 1
921
Disconnect switch 2
922
Disconnect switch 3
923
Disconnect switch 4
924
Disconnect switch 5
925
Disconnect switch 6
926
Disconnect switch 7
927
Disconnect switch 8
928
Disconnect switch 9
929
Disconnect switch 10
930
Disconnect switch 11
931
Disconnect switch 12
932
Disconnect switch 13
933
Disconnect switch 14
934
Disconnect switch 15
935
Disconnect switch 16
936
Disconnect switch 17
937
Disconnect switch 18
938
Disconnect switch 19
939
Disconnect switch 20
940
Disconnect switch 21
941
Disconnect switch 22
942
Disconnect switch 23
943
Disconnect switch 24
968
Breaker 1
969
Breaker 2
970
Breaker 3
971
Breaker 4
972
Breaker 5
973
Breaker 6
1012
Thermal overload protection 1
1013
Thermal overload protection 2
Bitmask
Element
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communications Failure
9
Voltage Monitor
10
FlexLogic Error Token
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...