GE Multilin
B30 Bus Differential System
4-3
4 HUMAN INTERFACES
4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
4
Before backing up settings and upgrading, set the
Settings > Product Setup > Security > Dual Permission Security
Access > Remote Setting Authorized
and
Local Setting Authorized
settings to "ON." Otherwise, the upgrade is blocked
and results in an "Unable to put relay in flash mode" message.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of firm-
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The
EEPROM DATA ERROR
message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
4.1.4 ENERVISTA UR SETUP MAIN WINDOW
The EnerVista UR Setup software main window supports the following primary display components:
1.
Title bar that shows the pathname of the active data view
2.
Main window menu bar
3.
Main window tool bar
4.
Site list control bar window
5.
Settings list control bar window
6.
Device data view windows, with common tool bar
7.
Settings file data view windows, with common tool bar
8.
Workspace area with data view tabs
9.
Status bar
10. Quick action hot links
NOTE
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...