IF 632 Installation and Operation Manual
Release: 3 01/31/01
29
SYSTEM OPERATING CONDITIONS
Default Mode
WARNING NOTE
When shipped from the factory, the Identiflex 632 system has been initialized to a
minimal "default" configuration as part of our system testing procedures. It is
important that the system be re-initialized utilizing the SmartStart
feature upon
installation, after all of the input and output devices have been connected. This will
result in a customized default configuration.
The IF632 System will not recognize or communicate with any of the
connected devices until the SmartStart
process has been exercised. The
IF632 will not report an alarm until this process has been completed. Refer
to the programming section of this manual for details about activating
SmartStart
.
After the SmartStart
routine has re-initialized the IF632, the system will be
configured as follows:
1. All (input) initiating points are configured to be "Automatic" initiating points
(standard smoke detector points). Point Identification Devices (PID's) shall be
configured as manual stations if the priority interrupt is set.
2. The system defaults to Access Level #2.
3. Whenever any input point(s) goes into alarm:
A.
All output signaling circuits activate and produce a steady, 24VDC output.
B.
All output relays are activated.
C.
The city-tie and common alarm relays activated.
Normal Quiescent
Condition (default)
When the system is in the normal quiescent condition, the green "Power On" LED is
illuminated indicating the system is operating from normal AC line power. All input
and output circuits are "normal" (no alarm or trouble conditions). All other LED's
and alphanumeric display are extinguished. The system internal buzzer is silent. To
view system status message, press "
Enter
". Refer to Figure
O-1. All Series 600 Relay Modules and Building Control Modules programmed
with feedback will have the associated LED illuminated indicating either an active or
inactive relay position. All other indicators will be extinguished.
In the normal condition, the green "Power-On" LED will be 'ON' - steady. All other
indicators will be extinguished.
NOTE
:
The system is equipped with a built-in screen saver.
When the system remains in the idle mode (i.e. normal quiescent
condition) for over 15 seconds the screen will automatically go
blank.
Status :Normal
MM/DD/YY HH:MM
System Idle
Figure O-1
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...