IF 632 Installation and Operation Manual
Release: 3 01/31/01
17
Programming
WARNING!
In order to properly prepare the inputs and
outputs required for Releasing, very specific programming steps
must be performed. Failure to follow these steps could result in
failure of the suppressant to be discharged, or there could be
unplanned discharge of the suppressant.
The following describes the steps to be taken to program the IF 632 FACP for releasing. The detailed programming
instructions can be found in Section 4 Programming.
In order to create a Releasing sub system, it is necessary to select and program Input devices, Control devices, and Output
devices.
Input
Devices
Select the first initiating device to activate Releasing, program it as an AND zone and Assign Input Group X
Select the 2nd initiating device to activate Releasing, program it as an AND zone and Assign Input Group X
Control
Devices
Select the input device for the Abort switch, program it as an Abort zone and Assign Input Group X
Select the input device for the Dump switch, program it as a Dump zone and Assign Input Group X
Output
Devices
Select the Signal Circuit (Conventional) to sound the audible alarm, program it’s Alarm Level (ALR:2) to Releasing
and it’s Signal type (SIG:XXX) to Releasing. Program the Output Group to Y.
Select the Releasing Solenoid Module (RSM-95) to control the releasing solenoid, program it’s Alarm Level (ALR:3)
to Releasing. Program the Output Group to Y.
Tying it together
Program the Control By Event (CBE) table to have Input group X activate Output Group Y
IMPORTANT
Only the Analog Addressable Device RSM-95 with a SID module, installed in accordance with the Wiring Drawing
A-W532-1 should be used to actuate the Releasing Solenoid. This device is Bypassed during a SmartStart to prevent
accidental discharge , should inputs be activated during the generic configuration. After a SmartStart, the correct
configuration should be uploaded to the FACP, the Releasing Solenoid disconnected from the RSM-95, and the
Bypass removed from the RSM-95. After determining that the RSM-95 is not active, the solenoid should be
reconnected.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...