![Gamewell IDENTIFLEX 632 Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/gamewell/identiflex-632/identiflex-632_installation-and-operation-manual_3365645097.webp)
IF 632 Installation and Operation Manual
Release: 3 01/31/01
97
Figure 8
>>
NOTE: The display starts with Circuit 1 and begins with
the highest address in circuit.
Field Descriptions
“Ckt”: xx"
Indicates the circuit (analog line or conventional) address that has
been selected.
"Add: xxx"
Shows the address of the analog device to be modified (1 - 126).
"D_Type:xxx"
“Comp:x”
“Sens:x”
“R/R:x”
“FTemp:x”
Shows the type of device (from type code of addressed device). If
the device type is a photo detector, Figure 8A will be displayed. For
a complete list of Device Types refer to Table P3.
A photo detector can be selected for operation with background
compensation (Yes) or without background compensation (no).
Default is Yes.
The sensitivity range of a photo detector can be adjusted
(compensated) to the environment. The device sensitivity range; 3
is the least sensitive and 0 is the most sensitive. The default is ‘2’.
If the device is a heat detector, Figure 8B will be displayed. If the
device is a heat detector, the temperature can be defined in Celsius or
Fahrenheit.
"Z_Type: xxx"
Shows the type of zone that has been selected for the device. Zone
types are defined in Zone Type Table P2.
"I_GRP: x"
Indicates the selected initiating group of the device. Each input
device can only be assigned to one group. One initiating group can
contain many input devices (logically arranged). The user can utilize
up to 256 initiating groups.
"W1:xxx "
Indicates the five (5) separate word dictionaries (W1 - W5) stored
and words contained in each dictionary (0 - 127 coded words for
Dict. 1 - 4, and 0 - 1024 for Dict. 5). This field is not displayed until
selected. Refer to Table P4.
>>
NOTE: The user can scroll through field variables using
up/down arrow keys or enter the address number directly
via the key pad.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...