IF 632 Installation and Operation Manual
Release: 3 01/31/01
19
SYSTEM MODULAR CONSTRUCTION
Common Control
Section
The common control section consists of four modules; the operators display, the bus
driver module, a relay expansion module, and the main CPU module. An optional RS-
232 interface module is available for interface to the system CPU.
Operators
Display Module
The operators display module is the main user interface to the IF632 system. It
includes the interactive, 4 line by 40 character, alphanumeric display, the LED
indicators and tactile switches. The operators display module provides the user with
visual indications and guided prompts during all operating and programming
functions. All alarms, faults, or supervisory actions, as well as system operating
conditions (
Normal, Alarms, Faults)
are shown on the alphanumeric display. LEDs
provide indication, and prompt the user response to the next sequential action. The
"Power On" LED indicator is green, alarms or activated signal circuits and city tie are
indicated by red LED's. Faults and user prompts are indicated by yellow LED's.
There are four arrow keys for scrolling through events and selecting functions.
Bus Driver
Module
The bus driver module (BDM) contains the circuitry that interfaces with the CPU and
system modules. It is equipped with two Style Y or Z, limited energy signaling circuits
(2 amps maximum each) and a city tie circuit. It has three power limited outputs for
24 Vdc auxiliary power, 12 Vdc, and resetable 24 Vdc smoke detector power. The
BDM also monitors the status of the CPU for transfer to default alarm mode of
operation.
Relay Expansion
Module
The common relay module provides 4 form C (SPDT) common relay outputs. These
relays transfer during
Common
Alarm, Common Trouble,
and
Supervisory
. The
common contact on each relay is fused with a 10 amp fuse. Each relay has a monitor
terminal (positive feedback), for status indication of the controlled device. The
common relay module mounts (via standoffs) to the right side of the bus driver
module. A fourth relay is provided for optional applications.
CPU Module
The CPU module (or microprocessor module) contains the system operating firmware
and non-volatile memory. A serial communications port is provided for connection to
peripheral devices. All user programmed memory is backed up via its on board
lithium battery.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...