IF 632 Installation and Operation Manual
Release: 3 01/31/01
20
SYSTEM I/O COMPONENTS
IF632 Analog
Addressable
Module
The IF632 analog addressable module, monitors and controls the Gamewell Series 95
analog addressable devices. The module can be configured with either one (AAM95-1),
two (AAM95-2) or four (AAM95-4) analog circuits. Each circuit is capable of
monitoring and controlling up to 126 analog addressable devices. The analog
addressable module has its own microprocessor which provides communication between
the connected field devices and the Common Control. Each analog/addressable circuit
can be wired as a Style 4 (class B), or Style 6 (class A) analog/addressable circuit.
These circuits are suitable for limited energy wiring. Up to two AAM95-4 modules may
be installed in a IdentifFlex 632 system for a total of 1008 analog addressable points per
system.
Series 95
Input/Output
Devices
The IF632 system is designed to operate with Gamewell's Series 95 Analog Addressable
detectors (photoelectric, ionization and heat) and interface devices.
Other input devices include the Point Identification Device (PID-95), the Manual
Station (MS-95) and the Collective Zone Interface (CZI-95).
Analog Addressable output device include the Relay Control Element (RCE-95), the
Signal Control Element (SCE-95), the Building Control Element (BCE-95) and the City
Tie module (CTX-95).
____________________________________________________________________________________________
NOTE: The following display modules may be located over any Analog Addressable Module, Aux. Power Supply, or
empty module location.
Relay Control
Display
The 600 series
Relay Control Display
Module (RCD) provides 8 individual displays
with a Red (Active) and Yellow (Trouble) LED to indicate the status of user assigned
RCE-95 modules. Each display also includes a tactile switch for programming.
Signal Control
Display
The 600 series
Signal Control Display
Module (SCD) provides 8 individual displays
with a Red (Active) and Yellow (Trouble) LED to indicate the status of user assigned
SCE-95 modules. Each display also includes a tactile switch for programming.
Building
Control
Display
The 600 series
Building Control Display
Module (BCD) provides 8 individual
displays with a Green (ON Relay Active) and a Red (Off Relay Active) LED to
indicate the status of user assigned BCE-95 modules. Each display includes a tactile
switch for programming and rotary On/Auto/Off switch for manual control of the
BCE-95.
____________________________________________________________________________________________
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...