IF 632 Installation and Operation Manual
Release: 3 01/31/01
22
SYSTEM I/O COMPONENTS (CONTINUED)
____________________________________________________________________________________________
Building
Control
Module
The 600 series B
uilding Control Modules
, are designed to provide an On/Auto/Off
control function to building systems. The building control module is available in 4
(BC-4) or 8 (BC-8) circuit increments. Each circuit consists of two relays that provide
ON or OFF control when selected. Each relay is programmable for Form A or Form B
contacts. The relay contacts are rated at 10 Amps and fused to protect the controlled
circuits. Each circuit has a feedback point to provide positive confirmation that the
controlled function has occurred.
BCM Display
The building control module display provides LED status and manual control of each
circuit. Each display circuit comes with a tactile switch for programming and service
functions, a three position On/Auto/Off switch for manual override and two LEDs for
status indication. Green = ON relay active or Feedback point normal, red = OFF relay
active or Feedback point active.
____________________________________________________________________________________________
AM500
Module
The AM500 module allows the IF632 system to interface to Flex 500 devices. It has
been designed with 8 Class B circuits that will monitor 50 devices each. An optional
Class A module (AM500-SDA) is available. Up to two of these modules may be
installed in an IF632 system for a total capacity of monitoring 800 of the Flex 500
devices.
AM500
Display
The display module provides LED annunciation of
Alarm and Trouble
conditions. It
has one switch per circuit for programming and service functions and a location for a
user defined custom label.
____________________________________________________________________________________________
City Tie
Module
The 600 series
City Tie Auxiliary
Module (CTX-4) provide 4 additional, limited
energy, polarity reversal, city tie circuits. Each circuit is independently programmable
for selective operation.
City Tie
Module
Displays
The city tie auxiliary module display provides LED annunciation indicated by - red -
Alarm (active) and - yellow - Trouble. Each circuit has a tactile switch for
programming and service functions. A location for a user defined custom label is
provided on each circuit.
____________________________________________________________________________________________
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...