IF 632 Installation and Operation Manual
Release: 3 01/31/01
108
CBE Programming
Control-by-Event "CBE" programming is dedicated to system wide ALARM functions.
Select "CBE" (#2) from the main "Programming Mode" menu to change or assign input
group assignment with the associated output group.
To select "logical" Group Inputs
1. Select "CBE" (
2
) from the main "Programming Mode" menu.
2. Press "
Enter
".
Enter Input Group#: XXX
Figure 13
3. Using numeric keys, enter the corresponding input group number. The
group number will be displayed in the location as shown in Figure 14.
xxx
Enter Input Group: xxx
Figure 14
4. Enter all desired input group numbers. The assigned input group number
is displayed in top left of screen. As the next input group number is
entered, group numbers are sequentially arranged (ascending order). Enter
up to 256 group input numbers.
>>
NOTE: To cancel an individual input group, enter that group number
and press "Enter". The group number is not shown and is then
canceled.
xxx xxx xxx xxx xxx xxx xxx xxx xxx
xxx xxx xxx xxx xxx xxx xxx
Enter Input Group: xxx
Figure 14A
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...