![Gamewell IDENTIFLEX 632 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/gamewell/identiflex-632/identiflex-632_installation-and-operation-manual_3365645041.webp)
IF 632 Installation and Operation Manual
Release: 3 01/31/01
41
Module Identification and Placement
Modular
Functions
The IF632 system utilizes a unique addressing scheme that allows it to supervise
card placement and monitor
card types.
This addressing scheme monitors specific
pre-assigned module locations in the control panel as well as the expander cabinet.
The card locations are pre-defined that can not be altered. See Figure I-1.
Card numbered 0 through 7 are reserved for the various common control module
sections. These card location numbers are hardwired physical circuits. Card
locations 8 - 39 are assigned to specific cards and displays installed in the cabinet
bays.
Card Type
Code
Each module returns a
card type
code when polled by the main CPU. Card type
codes are fixed codes that are assigned to each module type. When a valid response
is detected to any of the addresses polled, a data base for the device is created in
memory. The specific card type codes which are read from these locations are
defined in Table I-3 below.
Card Locations
0 through 7
Cards numbered 0 through 7 identify the location of card types that reference the
common control section of the system. Specifically, the electronic module functions
are identified. These card location numbers reference hardwired physical circuits.
Card identification numbered 0 through 3 reference designated hardwired circuits
interconnecting to the common control display module. Card identification
numbered 4 - 7 reference designated hardwired circuits on the bus driver module.
Cards # 8 - 39
Card numbered 8 through 39 are individual modules physically installed in cabinet
bays In the IF632 only eight card and eight display locations are available. See
Installation Section 3, Figures I-1 and I-2 for cabinet layout. Each module (i.e. I/O
module or individual display) has programmable addressing jumpers (1, 2, 3 or 4)
which are designated on each module as S1. The addressing jumpers must be set
according to the physical placement in the cabinet bay locations. Set the module
addressing jumper (1 - 4) in the proper location as shown in Figures I-1 and I-2.
Module Bus
The Module bus interconnects the left I/O modules and the right I/O modules with
the bus driver module. The left I/O modules are linked (via ribbon cable) and
interface with the bus driver module at J5 connector (labeled I/O Left). The right
I/O modules are also interconnect (via ribbon cable) and interface with the bus
driver module at J8 connector (labeled I/O Right). Each I/O module occupies one
slot on the module bus.
The left I/O module displays are linked (via ribbon cable) and interface with the bus
driver module at J6 connector (Display Left). The right I/O module displays are
linked (via ribbon cable) and interface with the bus driver module at J7 connector
(Display Right). The addressing jumper of each display must match the associated
I/O module addressing jumper placement.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание IDENTIFLEX 632
Страница 25: ...Section 2 IDENTIFLEX 632 System Operation Technical Manuals Online http www tech man com firealarmresources com...
Страница 37: ...Section 3 IDENTIFLEX 632 Installation Technical Manuals Online http www tech man com firealarmresources com...
Страница 71: ...Section 4 IDENTIFLEX 632 System Test Mode Technical Manuals Online http www tech man com firealarmresources com...
Страница 85: ...Section 5 IDENTIFLEX 632 Programming Technical Manuals Online http www tech man com firealarmresources com...
Страница 145: ...Section 5A IDENTIFLEX 632 Appendix Technical Manuals Online http www tech man com firealarmresources com...