background image

INSTALLATION INSTRUCTIONS FOR

MPC-6000, MPC-7000 AND RND-2 DISPLAY BOARDS

Installation is to be done by qualified personnel who
have thoroughly read and understood this instruction
sheet.

Step 1.)

Upload the panel configuration to the CIS-4 software.

Step 2.)

Disconnect BATTERY and AC prior to working on
equipment.

Step 3.)

Remove cable connection from the keypad on the
Inner Front Plate to connector J3 on the Display
Board (P/N MPC(6/7)-DB, MPC6-DB2, RND2-DB or
RND2-DB2).

Step 4.)

Remove the cable assembly (P/N 555-446055) from
connector J1 of the Display Board (P/N MPC(6/7)-
DB, MPC6-DB2, RND2-DB or RND2-DB2).

Step 5.)

Remove the Display Board (P/N MPC(6/7)-DB,
MPC6-DB2, RND2-DB or RND2-DB2) from Inner
Front Plate Assembly by removing the four screws.
Place the screws to one side. Refer to Figure 1.

PLATE

906-220604 (4)

#6-32 x 1/4 SCREW

MPC-6000

ASS'Y

J3 - Keypad

Connection

Board

Display

to Main

J1 - Connection

Board

MPC-7000

showing Display
Board and Keypad

to Front Plate Ass'y

Board attached

showing Display

being attached
to Front Plate Ass'y

Figure 1

Display Board Removal/Installation

P/N 315-050139FA-0

Siemens Building Technologies, Inc.
8 Fernwood Road

Phone: (973) 593-2600

Florham Park, New Jersey 07932

Fax: (973) 593-6670

Web: www.faradayfirealarms.com

Step 6.)

If replacing an RND-2 display board, transfer the
panel firmware IC (U4, located in the socket at the
lower right corner of the board as shown in Figure 2)
from the old board to the new one by following the
steps listed below.

U4

J2

R13

S1

U21

U2

U5

U6

J9

U12

J1

J3

Replace U4

U4

Figure 2

Replacing U4 on RND-2

a.

Note where and how the IC is positioned.

b.

Use a DIP extraction tool to remove U4 from its

socket on the new display board and then discard this
IC. If an extraction tool is not available, a short, thin
blade screwdriver may be used.

c.

Remove U4 from the old display board. Insert

this IC into the proper socket on the new display
board. Press down firmly to seat the IC properly in
the socket.

CAUTION:

Make sure the "U" cut in the new IC is positioned as it
was in the old IC (if appropriate). Check that the IC is
properly seated in the socket and that all the IC pins
are properly aligned.