The
Low Scale
and
High Scale
fields are shown for analog input types only. They are used to set the display
range for the input in order to scale the 0(2)-10Vdc or 0(4)-20mA signal. The display value is then a linear
representation of the input signal from the low to high scale value.
Once all of the settings have been made for the monitor point, press the
“Done” button to return to the Monitor
Setup screen.
4.3.1.1
Important Settings for Using Loop Input 2 as Monitor Points
Decimal Point
When using the second input of control loops for monitor points, it is important to note
that the controller itself, provides range, calibration and input bias settings for the input.
In order for the MCT to properly read and display the value, the decimal point setting for
the monitor input must match that of the loop control for input 2. If the decimal point
settings do not match between the MCT and the loop controller, the MCT will not properly
read or display the value of the second input for the monitor point.
Engineering Units
When degrees C or degrees F is selected from the Degrees C/F screen in the MCT
runtime application, engineering units for temperature of
“C” or “F” are automatically
updated for all loop and monitor points. If input 2 of the loop controller is a temperature
reading in degrees F for example (from a temperature transmitter), and degrees C is
selected on the MCT, the monitor point reading will be a value in degrees F, but the units
shown will be in degrees C.
To prevent the units from being changed, the Degrees C/F settings screen in the runtime
application can be hidden to prevent changes (see section 4.7 Functions) or even
password protected in the runtime application. The engineering units could also be
entered as
“degC” or “degF” for example. The MCT will then ignore them for a degrees
C or degrees F units change.
It is important to ensure that the engineering units match the loop control for input 2 to
avoid operator confusion and prevent the misinterpretation of the value.
Input Offsets
When using the second input of control loops for monitor points, it is important to note
that the controller itself, provides range, calibration and input bias settings for the input.
The MCT does provide an input offset capability which can be used to correct errors in
readings from the analog, RTD or thermocouple monitor modules in order to correct for
lead resistance or sensor tolerance.
The
“Input Offset” screen in the MCT runtime application also allows an offset to be
applied to the monitor points when input 2 of the loop controls are used. However, the
input offset of the MCT only corrects the value shown on the MCT and does not offset
the reading on the loop control.
If the loop control is visible to the operator, it is recommended that the
“Input Offset”
screen be hidden (see section 4.7 Functions) or even password protected in the runtime
application to prevent an offset from being applied to the monitor point in the MCT.
Rather, use the input bias setting of the loop control so that both the reading on the loop
control and the MCT will match to avoid operator confusion.
Содержание MCT-CM
Страница 1: ...MCT CM User Manual MCT CM User Manual Rev C August 2022 V1 2eCM30 V1 3eCM22 Supersedes May 2021...
Страница 20: ...MCT CM 20...
Страница 24: ...MCT CM 24...
Страница 45: ...MCT CM 45...
Страница 187: ...MCT CM 187...
Страница 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Страница 228: ...MCT CM 228...
Страница 229: ...MCT CM 229...
Страница 230: ...MCT CM 230...
Страница 231: ...MCT CM 231 Analog I O Card...
Страница 232: ...MCT CM 232...
Страница 233: ...MCT CM 233 Digital Input Card...
Страница 234: ...MCT CM 234...
Страница 235: ...MCT CM 235 Digital Output Card...
Страница 236: ...MCT CM 236...
Страница 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Страница 238: ...MCT CM 238 A 5 Power Supply Specifications...
Страница 239: ...MCT CM 239...
Страница 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 241: ...MCT CM 241...