MCT-CM
152
NOTE:
Any changes made to the above settings must be saved in order for them to take effect. When changes
are complete, press the
‘Save’ button to save the new settings in order to use them.
The
Bar Code Test
field allows the operator to test the operation of the barcode scanner. As a bar code is
swiped by the reader, the scanned value will appear in this field. If upon scanning a bar code, no value appears
in this field, check the wiring and communication settings of the barcode scanner to be sure that it is connected
and set up properly.
9.9.1
Barcode Reader Communication Settings
In order for the barcode scanner to communicate properly with the MCT, it must be set with the proper
communication settings. This includes baud rate, data bits, stop bits, parity and start/end of transmission
characters as follows:
Baud rate = 9600 baud
Data bits = 7
Stop bits = 1
Parity = even
Preamble = STX (0x02)
Postamble = ETX (0x03)
The preamble and postamble are the start of transmission and end of transmission characters that must be
used to frame the barcode transmitted to the MCT so that it recognizes the beginning and end of the
transmission. All other terminator, BCC, ACK and/or handshaking characters must be disabled.
9.9.1.1
Setting up the Unitech MS-120-2 Barcode Scanner
The following instructions are provided for the Future Design Controls recommended Unitech MS-120-2
barcode scanner. These instructions do not apply to other makes or models of scanner. Consult the
manufacturer’s manual for other makes or models for information on how to set the proper communications
settings.
NOTE:
The steps below are assuming manufacturer default settings are in place. If the scanner settings are
unknown, restore the scanner to manufacturer defaults by scanning barcode ‘enter group 1’ on page
5 of the MS-
120 Series Programming Manual and then scanning the ‘factory defaults’ barcode at the
bottom of page 5. Scan ‘exit’ to complete the process.
For communication settings see page 11 (RS232 Serial Setting) of the MS-120 Series Programming Manual
Step 1
scan barcode at top of page 11 for ‘enter group 4’
Step 2
scan barcode C2 for parity on page 12 and then scan the barcode for the number 0 on page 11
Step 3
scan barcode C3 for data bit on page 12 and then scan the barcode for number 0 on page 11
Step 4
scan the barcode for ‘exit’ on page 11 to complete RS232 settings
For pre/postamble settings see page 13 (Scanner) of the MS-120 Series Programming Manual
Step 1
scan barcode at top of page 13 for ‘enter group 5’
Содержание MCT-CM
Страница 1: ...MCT CM User Manual MCT CM User Manual Rev C August 2022 V1 2eCM30 V1 3eCM22 Supersedes May 2021...
Страница 20: ...MCT CM 20...
Страница 24: ...MCT CM 24...
Страница 45: ...MCT CM 45...
Страница 187: ...MCT CM 187...
Страница 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Страница 228: ...MCT CM 228...
Страница 229: ...MCT CM 229...
Страница 230: ...MCT CM 230...
Страница 231: ...MCT CM 231 Analog I O Card...
Страница 232: ...MCT CM 232...
Страница 233: ...MCT CM 233 Digital Input Card...
Страница 234: ...MCT CM 234...
Страница 235: ...MCT CM 235 Digital Output Card...
Страница 236: ...MCT CM 236...
Страница 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Страница 238: ...MCT CM 238 A 5 Power Supply Specifications...
Страница 239: ...MCT CM 239...
Страница 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 241: ...MCT CM 241...