MCT-CM
38
3.5.3
RTD Module (IO-6RTD) Input Wiring
The IO-6RTD module is a 6 RTD input module. The module can accommodate either 2 or 3 wire RTD sensors.
The RTD inputs are isolated from the internal logic. DIP-switch 9 is used to select the upscale or downscale
value for sensor break detection. A value of 32,768 is used to indicate upscale break and a value of
–32,767
is used to indicate downscale break.
NOTE:
DIP switch 8 is not used with the RTD module so its position does not affect operation. As there is
no inter-channel isolation, isolated RTD's must be used in order to prevent ground loops and reading
errors.