The
Defrost Type
selection is used to choose the defrost mode. Available selections are Disabled, Timed
Defrost and Timed Process. When Timed Defrost is selected, defrost occurs on regular intervals based on the
interval time entered on the defrost screen in the MCT runtime application. When Timed Process is selected,
defrost also occurs on regular intervals based on the interval time entered on the defrost screen in the MCT
runtime application; however, the selected enable loop/monitor must also be below the enable setpoint.
The interval timer will begin counting down to the next defrost as long as the selected enable loop/monitor
remains below the enable setpoint. If at any time the selected loop/monitor rises above the setpoint, the defrost
interval timer will be reset. This provides a means for enabling defrost only when the control loop or monitor
point associated with the function is below a certain temperature in which defrost may be required on regular
intervals.
The
Enable Loop/Monitor
selection is shown only when defrost is set to timed process. These fields are used
to select any of the available loop or monitor points configured in the system to be used as the enable point for
defrost.
When a loop is selected as the enable source:
The set point of the selected loop is used as the source value and is compared to the defrost enable set point.
When the loop set point is equal to or less than the defrost enable set point, the defrost logic will be activated.
This insures that defrost will operate as required, since temperatures can rise if the cooling coil begins to ice
over and cooling capacity is lost. If the air temperature was used, the coil could ice over causing air temperature
to rise, preventing defrost from activating when it is required.
When a monitor point is selected as the enable source:
The process value of the selected monitor point is used as the source value and is compared to the defrost
enable set point. When the monitor point is equal to or less than the defrost enable set point, the defrost logic
will be activated. This offers the ability to provide a type of “adaptive” defrost by placing the sensor on the
cooling coil or cold plate and monitoring surface temperature. It could then be used to activate defrost only
when the surface temperature is operating at or below freezing in which ice can accumulate.
The
Enable
Setpoint field is shown only when defrost is set to timed process. It is used to enter the setpoint
for the selected enable loop/monitor below which the defrost interval timer will be started.
The
Terminate
Setpoint field is shown only when defrost is set to timed process. It is used to enter the setpoint
for the selected enable loop/monitor above which the active defrost will be stopped and the precool period
started. When used in conjunction with a monitor input to measure coil temperature for example, it allows
defrost to be stopped once the coil temperature has risen to a point at which all ice would be melted off. This
allows regular conditioning to resume earlier than waiting the entire defrost duration.
Содержание MCT-CM
Страница 1: ...MCT CM User Manual MCT CM User Manual Rev C August 2022 V1 2eCM30 V1 3eCM22 Supersedes May 2021...
Страница 20: ...MCT CM 20...
Страница 24: ...MCT CM 24...
Страница 45: ...MCT CM 45...
Страница 187: ...MCT CM 187...
Страница 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Страница 228: ...MCT CM 228...
Страница 229: ...MCT CM 229...
Страница 230: ...MCT CM 230...
Страница 231: ...MCT CM 231 Analog I O Card...
Страница 232: ...MCT CM 232...
Страница 233: ...MCT CM 233 Digital Input Card...
Страница 234: ...MCT CM 234...
Страница 235: ...MCT CM 235 Digital Output Card...
Страница 236: ...MCT CM 236...
Страница 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Страница 238: ...MCT CM 238 A 5 Power Supply Specifications...
Страница 239: ...MCT CM 239...
Страница 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 241: ...MCT CM 241...