MCT-CM
173
Alarms for information on assigning the alarm to the digital output.
NOTE: If more than one loop/monitor alarm is assigned to the output, the output
will not operate correctly and may cycle on and off uncontrollably. Do not
assign more than one alarm to an output.
Digital Input Alarm:
When selected, the output will turn on when the selected digital input alarm occurs.
The output will stay on until the alarm is silenced. The selected digital input must be
configured as an alarm input or the output will not operate.
Digital Input Control:
When selected, the output will turn on and off based on the selected input status.
The input acts as the switch to turn the digital input on and off. The selected digital
input must be configured for digital output control or the output will not operate.
*Remote Alarm (NC):
When selected, the output
acts as a ‘fail-safe’ fault output. When no alarm is present,
the output will be energized. Any alarm in the MCT will de-activate the output. When
the alarm ‘Reset’ button is pressed on the Alarm screen, the output will turn back on.
When used in conjunction with the repeat time setting, the output will automatically
turn back off, after the repeat time period, if any alarm condition is still present.
Defrost:
When selected, the output will turn on during an active defrost cycle. When defrost
is inactive or the fan delay is active, the output will be off. See section 9.1 Defrost for
more information on defrost operation.
NOTE: When redundant system operation is enabled in the configuration, this
output will only operate when defrost is active and system 1 is the primary
system.
Precool:
When selected, the output will turn on during the fan delay period after a defrost
cycle. When defrost is inactive or a defrost cycle is in progress, the output will be off.
See section 9.1 Defrost for more information on defrost operation.
NOTE: When redundant system operation is enabled in the configuration, this
output will only operate when precool (fan delay) is active and system 1 is
the primary system.
Redundant System 1:
When selected, the output will turn on when system 1 is selected for operation based
on system redundancy settings. See section 9.2 Redundancy for more information
on redundant system operation.
Redundant System 2:
When selected, the output will turn on when system 2 is selected for operation based
on system redundancy settings. See section 9.2 Redundancy for more information
on redundant system operation.
Defrost 2:
When selected, the output will turn on during an active defrost cycle of redundant
system 2. When defrost is inactive or the fan delay is active, the output will be off.
See section 9.1 Defrost for more information on defrost operation.
Precool 2:
When selected, the output will turn on during the fan delay period after a defrost cycle
of redundant system 2. When defrost is inactive or a defrost cycle is in progress, the
output will be off. See section 9.1 Defrost for more information on defrost operation.
Содержание MCT-CM
Страница 1: ...MCT CM User Manual MCT CM User Manual Rev C August 2022 V1 2eCM30 V1 3eCM22 Supersedes May 2021...
Страница 20: ...MCT CM 20...
Страница 24: ...MCT CM 24...
Страница 45: ...MCT CM 45...
Страница 187: ...MCT CM 187...
Страница 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Страница 228: ...MCT CM 228...
Страница 229: ...MCT CM 229...
Страница 230: ...MCT CM 230...
Страница 231: ...MCT CM 231 Analog I O Card...
Страница 232: ...MCT CM 232...
Страница 233: ...MCT CM 233 Digital Input Card...
Страница 234: ...MCT CM 234...
Страница 235: ...MCT CM 235 Digital Output Card...
Страница 236: ...MCT CM 236...
Страница 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Страница 238: ...MCT CM 238 A 5 Power Supply Specifications...
Страница 239: ...MCT CM 239...
Страница 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Страница 241: ...MCT CM 241...