3.3 Programming Mode
3-15
Chap. 3
OP
ERA
T
ION US
ING
THE
K
EYP
AD
Figure 3.7 Drive Monitoring Status Transition
Basic key operation
(1) With the menu displayed, use the and keys to select "Drive monitoring" (
3.oPE
).
(2) Press the
key to display the desired code in the monitoring items list (e.g.
3_00
).
(3) Use the and keys to select the desired monitoring item, then press the
key.
The running status information for the selected item will appear.
(4) Press the
key to return to the monitoring items list. Press the
key again to return to the
menu.
If the menu cannot switch to any other one, set function code E52 to 2 (Full-menu mode).
Displaying running status
To display the running status in hexadecimal format, each state has been assigned to bit 0 to 15 as
listed in Table 3.6. Table 3.7 shows the relationship between each of the status assignments and the
LED monitor display. Table 3.8 gives the conversion table from 4-bit binary to hexadecimal.
Table 3.6 Running Status Bit Allocation
Bit
Notation
Content
15
BUSY
1 when function code data is being written.
14
Always 0.
13
WR
Always 0.
12
RL
1 when communications is effective (when run commands and set frequencies
commands are issued via communications).
11
ALM
1 when an alarm has occurred.
10
DEC
1 during deceleration.
9
ACC
1 during acceleration.
8
IL
1 during current limitation.
7
VL
1 under voltage control.
6
TL
Always 0.
5
NUV
1 when DC link circuit voltage has increased up to the specified level (0 for
undervoltage).
4
BRK
Always 0.
3
INT
1 when the inverter output is shut down.
2
EXT
1 during DC braking.
1
REV
1 during running in the reverse direction.
0
FWD
1 during running in the forward direction.
Содержание frenic mini series
Страница 1: ...USER S MANUAL Fuji Electric Co Ltd MEH446...
Страница 2: ...Compact Inverter User s Manual...
Страница 60: ...4 2 4 2 Drive Frequency Command Generator Figure 4 1 Block Diagram for Drive Frequency Command Generator...
Страница 62: ...4 4 4 3 Drive Command Generator Figure 4 2 Drive Command Generator...
Страница 66: ...4 8 Figure 4 3 d Terminal Command Decoder ORing with Link Commands Ignoring Link Commands...
Страница 68: ...4 10 4 5 Digital Output Selector Figure 4 4 Digital Output Signal Selector...
Страница 70: ...4 12 4 6 Analog Output FMA Selector Figure 4 5 Analog Output FMA Selector...
Страница 72: ...4 14 4 7 Drive Command Controller Figure 4 6 Drive Command Controller and Related Part of the Inverter...
Страница 74: ...4 16 4 8 PID Frequency Command Generator Figure 4 7 PID Frequency Command Generator...
Страница 81: ...Part 3 Peripheral Equipment and Options Chapter 6 SELECTING PERIPHERAL EQUIPMENT...
Страница 109: ...Part 4 Selecting Optimal Inverter Model Chapter 7 SELECTING OPTIMAL MOTOR AND INVERTER CAPACITIES...
Страница 124: ...Part 5 Specifications Chapter 8 SPECIFICATIONS Chapter 9 FUNCTION CODES...
Страница 134: ...8 3 Common Specifications 8 9 Chap 8 SPECIFICATIONS 8 3 Common Specifications...
Страница 135: ...8 10...
Страница 257: ...App H Replacement Information A 33 App FVR C11S vs FRENIC Mini...
Страница 261: ...Glossary This glossary explains the technical terms that are frequently used in this manual...